VP Flowscope DP
Description
Ren Engineering Solutions: VP Flowscope DP FLOW METER Energy Monitoring Device
The VPFlowScope® DP is the ultimate measurement tool for saturated compressed air flow measurements. The unique design enables you to take measurements in the discharge pipe of a compressor under 100% saturated conditions. You can combine the probe with two display module types or with a connector cap without display.
The VPFlowScope® DP flow meter is a patented differential pressure flow meter designed for accurate measurement of saturated and hot compressed air. This innovative 4-in-1 device simultaneously measures bi-directional flow, pressure, temperature, and total flow, giving you a complete insight into your compressed air system’s performance. Because it can be installed under pressure without interrupting production, it’s ideal for continuous operations. The VPFlowScope DP offers major benefits such as improved compressor efficiency, accurate performance monitoring, and reliable energy audits. Its built-in data logger and VPStudio software make it easy to analyze data, identify losses, and uncover energy-saving opportunities. Compact yet powerful, the VPFlowScope DP provides a cost-effective and practical way to optimize your compressed air network while ensuring process reliability and sustainability.
Efficiency Component
1. Energy Efficiency – Smart monitoring devices reduce energy demand through increased awareness of energy consumption. With smart meters, end-users can monitor, evaluate and reduce energy consumption.
Technical Information
FLOW SENSOR
Measuring principle: Differential pressure
Flow range: 20 … 200 mn/sec | 65 … 650 sfps. Bi-directional measurement (standard)
Accuracy:2% of reading over 1:10 range, under calibration conditions: please refer to the user manual for details
Recommended pipe diameter: 50 mm (2 inch) and up.
Reference conditions: 0 °C, 1013.25 mbar 32 °F, 14.65 psi – DIN 1343
Gases: Wet* and dry compressed air, nitrogen and inert gases
PRESSURE SENSOR
Pressure sensor range, standard: 0 … 16 bar | 0 … 250 psi gage
Accuracy: +/- 1.5% FSS (0 … 60 °C) | (32 … 140 °F)
Temperature: compensated
TEMPERATURE SENSOR
Temperature sensor range: -40 … 150 °C | -40 … 302 °F. Icing should be avoided
Accuracy :+/- 1 °C | 1.8 °F
DATA OUTPUTS
Digital: RS485, MODBUS RTU protocol
Analog: 4 … 20 mA single analog / pulse output, selectable via VPStudio software
DISPLAY/DATA LOGGER
Technology: Liquid Crystal (LCD)
Back light: Blue, with auto power save
Data logger: 2 million points memory
MECHANICAL & ENVIRONMENTAL
Probe lengths: 386 mm | 15”
Process connection: Compression fitting, 0.5” NPT thread
Pressure rating: PN16
Protection grade: IP52 | NEMA 12 when mated to display module, avoid upside down installation. IP63 | NEMA 4 when mated to connector cap, avoid upside down installation
Ambient temperature range: 0 … 60 °C | 32 … 140 °F. Avoid direct sunlight or radiant heat
Wetted materials: Anodized aluminum, stainless steel 316, glass and epoxy
Corrosion resistance: Highly corrosive or acid environments should be avoided
ELECTRICAL
Connection type: M12, 5-pin connector, female
Power supply: 12 … 24 VDC +/- 10 % Class 2 (UL)
Power consumption: 3.6 Watt +/- 10%. 150 mA +/- 10% @24VDC, constant over the entire flow range
UL/ CUL: 14 AZ, Industrial Control Equipment
CE: EN 61325-1 (2006), Class AEN 61000-6-1 (2007)